Chartek 1620CSP, Coating, Intumescent
Miscellaneous Coating
Coating, Intumescent
Chartek 1620CSP
Product Description
Insulation to provide Fire Integrity to Structural steel.
Product Ratings
Provides fire integrity for I sections and hollow sections up to 300Hp/A based upon a critical core temperature of 350oC, 400oC, 427oC, and 538oC. Chartek 1620CSP, in combination with HK-1 carbon fiber / glass fiber mesh, can be applied using methods in the manufacturer's application manual up to a thickness of 45mm. | | An assessment of the performance has been made from tests conducted in accordance with ISO TR 834-3 hydrocarbon time temperature curve as well as jet fire tests in accordance with ISO 22899 up to a fire duration period of 3 hours. | | The following extra thickness is to be applied for Jet fire scenarios: | | Fire durations up to: | 15 minutes - 0mm; 30 minutes - 1.5mm; 60 minutes - 2.0mm; | 90 minutes - 2.5mm; 120 minutes - 3.0mm; 180 minutes - 3.5mm |
Applicable Standards
IMO Resolution A.517(13) with hydrocarbon curve as outlined in the UK Department of Energy's document entitled "The Hydrocarbon Fire Resistance For Elements of Construction for Offshore Installations" and ISO 22899-1