FIRETEX M90/02 Epoxy intumescent for Steel Decks
Miscellaneous Coating
Coating, Intumescent
FIRETEX M90/02 Epoxy intumescent for Steel Decks
Product Description
Insulation to provide fire integrity of steel decks.Composed of Steel deck insulated on the stiffened side with an epoxy based intumescent coating system, FIRETEX M90/02,reinforced with embedded FIRETEX J220 scrim.
Product Ratings
Hydrocarbon pool fire H-0, H30, H60, H90,H120 and H150 rating for Decks. | | Provides fire integrity as detailed below with minimum FIRETEX M90/02 application thickness: | | H-0 Deck: 4.0 mm | H-30 Deck: 7.35 mm | H-60 Deck: 9.93 mm | H-90 Deck: 11.71 mm | H-120 Deck: 13.50 mm | H-150 Deck: 15.06 mm | | as demonstrated by testing conducted as per IMO FTP Code Resolution A.754(18) with hydrocarbon curve as defined by UK Department of Energy. | | The density of FIRETEX M90/02 is 1000 kg/m3 independently verified from Exova Warrington Fire as per letter Exova Letter reference 309675 CL Dated 12th September 2010.The analysis followed the methodology given in Sherwin-Williams' test method LTM130. | | The Jet fire scale up thickness i.e addtional jet fire erosion factor on steel decks to be added to the above thickness are as following: | | Time (mins) JF add-on (mm) | 30 0 | 60 1.6 | 90 4.1 | 120 6.6 | 150 NA
Applicable Standards
Testing in accordance with IMO Res. A.754(18) with temperature-Time curve as specified in Department of Energy Test Specification - Issue 1: January 1990
Jet fire resistance test in accordance with ISO 22899-1/2: 2007
NA
NA