H-60/H-120 Corrugated Steel Fire Wall - fire towards either …
fire Protection - Partitions & outfits
Class H Partitions and Decks
H-60/H-120 Corrugated Steel Fire Wall - fire towards either side
Product Description
"H-60/H-120 Corrugated Steel Wall- fire towards either side"
composed of 2 mm corrugated steel wall insulated on one side with FireMaster Marine Plus Blanket (density 70 kg/m3), thickness 110 mm (one layer 50 mm and one layer 60 mm) in between and over the corrugations, and with 150 mm (3 layers of 50 mm blanket) inside corrugation.
The joints between blankets in each layer shall be arranged so that they should not coincide to the same location and are therefore offset by up to approximately half a blanket width. The nominal blanket width is 610 mm and is to be compressed to a width of 600 mm at joints.
The blankets are held in place by steel pins (Ø 3 mm / typically 12 to 25 mm longer than the blanket length) welded to the wall and Ø 38 mm friction-fit steel washers.
The installation is to be performed according to the manufacturers Method Statement FM-MS 01 PW and Fire Protection Systems Information reference FM 4.95.
Product Ratings
Not Available / To be Updated
Applicable Standards
Not Available / To be Updated