Unitor X-Flow Accommodation System, Water Based Fixed Fire Extinguishing System
Fire Extinguishing Systems and Equipment
Water Based Fixed Fire Extinguishing System
Unitor X-Flow Accommodation System
Product Description
Fixed Fire Extinguishing System equivalent to SOLAS Regulations II-2/10.6.1 & 10.6.2 and IMO FSS Code, Chapter 8. The system comprises pump units (master pumps, standby pump and pilot pump), pressure tank in combination with N2 cylinder, alarm section valves NHP-Z 2 AM and stop valves, water spray pendant nozzles NHP 18B, NF18B OP25, NF18B OP50 F2 & F1.5, NF CO46, NF CA12, NF18A-CA26, NF 18A-SS and pump motor starters. The system is an automatically operated wet system.
Product Ratings
Nominal release temperature: 57 deg. C. | Bulb color: Orange. | Working pressures / k-factors: NF18A-SS: 3.4 bar/ 33.1 (kg/min)/bar^0.5; NF18A-CA26: 3.4 bar/31.3 (kg/min)/bar^0.5; NHP 18B: 4.2 bar/18.6 (kg/min)/bar^0.5, NF18B OP25: 3.8 bar/ 27.9 (kg/min)/bar^0.5; NF 18B OP50 F2 or F1.5: 3.4 bar/ 29.9 (kg/min)/bar^0.5; NF CA12: 4 bar/ 14.47 (kg/min)/bar^0.5; NF-CO46: 3.8 bar/ 27.53 (kg/min)/bar^0.5. |
Applicable Standards
SOLAS (2014 Consolidated Edition) Regulation II-2/10.6.1 and 10.6.2,
IMO FSS Code (2015 Edition) Chapter 8/2.1.2,
IMO Resolution A.800(19) (adopted on 23 November 1995) as amended by Resolution MSC.265(84) (adopted on 9 May 2008).