Ultra Fog Fixed Water Based Local Application System
Fire Extinguishing Systems and Equipment
Water Based Fixed Fire Extinguishing System
Ultra Fog Fixed Water Based Local Application System
Product Description
The water mist system is composed of nozzle heads, stainless steel piping, manual or automatic section valves, filter, control system and water supply pump/s. , Under standby condition the system is pressurised till the section valve/s. The piping from section valve/s (normally closed) to the open nozzle heads is dry pipe. , When system is activated, the high pressure pump/s supply fresh water from dedicated freshwater tank at high pressure to the open nozzles via activated section valve/s.
Product Ratings
System normal working pressure is minimum 100 bar at the nozzle. | For nozzle 202-240-080-O is the spacing between nozzles 5m, and heights between the ceiling and the top of the protected object can be between 0,5 to 4m. | For nozzle 202-151-O is the spacing between nozzles 3m, and heights between the ceiling and the top of the protected object can be between 3 to 11.5m.
Applicable Standards
SOLAS Consolidated Edition 2014, Chapter II-2, Regulation 10, Sub-section 5.6.2
IMO MSC Circular 913 - GUIDELINES FOR THE APPROVAL OF FIXED WATER-BASED LOCAL APPLICATION FIRE-FIGHTING SYSTEMS FOR USE IN CATEGORY A MACHINERY SPACES (4-Jun-1999)
IMO FSS Code (2015 Edition) Chapter 6