Fire Eater Control Inert series IV8 (Inergen 200 & 300 bar g…
Fire Extinguishing Systems and Equipment
Fixed Fire Extinguishing System
Fire Eater Control Inert series IV8 (Inergen 200 & 300 bar g)
Product Description
Total flood Inergen fixed gas fire extinguishing system, equipment comprising of high pressure cylinders, valve assembly, system actuation units, nozzles, electrical components and electronic equipment.
Product Ratings
Ratings in accordance with Danish Institute of Fire Technology Test Report E-98097-01, dated 8/1999. (1) The minimum design concentration for net volume total flooding of Machinery Spaces and Pump Rooms is 46.2% v/v minimum at the lowest expected minimum ambient operating temperature (not greater than 0 C) and a maximum design concentration of 52% v/v (NOAEL) at 50 C.
Applicable Standards
IMO MSC/Circ.848 as amended by MSC.1/Circ.1267 dated 4 June 2008;
SOLAS Reg. II-2/10.4 (2014 Consolidated Edition);
FSS Code Chapter 5 (2015 Edition);