Autronica DCP Fixed System, Fixed Dry Chemical Fire Extinguishing Systems
Fire Extinguishing Systems and Equipment
Fixed Dry Chemical Fire Extinguishing Systems
Autronica DCP Fixed System
Product Description
“Autronica DCP Fixed System” A fixed installation based fire extinguishing system for use in gas fuel bunkering station areas. Main composition: A 2L/1.3 kg CO2 pilot gas cylinder fitted in a release cabinet connected with rubber hoses and SS tubing to a 40L/150 bar N2 cylinder that provides propellant gas via a pressure reducing valve (set point: 16 bar) and 15 mm SS tubing to a 200 kg dry chemical powder tank (safety valve set point: 16.5 bar). An automatically activated main valve (set point: 10 bar) on the powder tank feeds extinguishing powder through stainless steel distribution piping (DN50/40/25/20) to 8 pcs. 60°, ½” spiral jet nozzles.
Product Ratings
Not Available / To be Updated
Applicable Standards
Not Available / To be Updated