Skip to main content

SDS-72, Fixed fire detection and alarm systems components - Smoke detectors

Product Category Icon
Product Category:
Fire Detection and Alarm System

Product type  Icon
Product Type:
Fixed Fire Detection and Alarm Systems Components - Smoke Detectors

Product name
Product Name:
SDS-72
Product Description
Product Description

The smoke detection system SDS-72 is a sample extraction smoke detection system for up to 72 detection lines for cargo holds onboard ships. , , Main Components:, 1. ADP-3500 : Adapter module, 2. SDS-3000 : smoke detection panel (without detection lines), 3. SDS-3104 : smoke detection panel (1-4 detection lines), 4. SDS-3108 : smoke detection panel (5-8 detection lines), 5. SDS-3112 : smoke detection panel (9-12 detection lines), 6. SDS-3208 : Extension panel (5-8 detection lines), 7. SDS-3212 : Extension panel (9-12 detection lines), 8. SDS-3216 : Extension panel (13-16 detection lines), 9. SDS-3300 : smoke detection unit SDU, 10. SDS-3500 : remote panel, 11. SDS-3600 : junction box (for SDS-M0460), 12. SDS-3700 : junction box (for SDU), 13. SDS-3800 : 3/2-way flap, 14. SDS-M0440 : fan unit (230 VAC), 15. SDS-M0441 : fan unit (110VAC), 16. SDS-M0460 : fan module, , The SDS-72 are available in three variants with hardware combinations listed above:, Variant A: The sampling pipes for all cargo holds run separately into the CO2 room, where they are connected via 3/2-way-valves to the smoke detection panel. Variant A is designated for the connection of sampling pipe diameters DN20/DN25., Variant B: The sampling pipes for all cargo holds run separately into the CO2 room and the main components of the smoke detection system are located in the CO2 room. Variant B is designated for the connection of sampling pipe diameters DN32 to DN150., Variant C: The sampling pipes for all cargo holds run separately into the suitable passage way beneath the cargo holds, where they are connected via valves to the smoke detection unit. The smoke detection unit is connected via loop isolator with the smoke detection panel. Variant C is designated for the connection of sampling pipe diameters DN32 to DN150., , Fan unit SDS-M0440/ SDS-M0441 or SDSD-M0460 is to be used in variants A, B or C according to the airflow volume requirements of each installation., , Software version: CM3100A-01.01.011, CM3100B-01.01.011

Product Ratings
Product Ratings

Power Supply: 220/230 V AC or 110/115V AC, 50/60Hz | Degree of protection: | - SDS-3000: IP22 | - SDS-3700: IP54 | - SDS-3300: IP54 | - SDS-32xx: IP54 | - SDS-31xx upper/lower component: IP54/IP22 | - SDS-M0440: IP54 | - SDS-M0441: IP54 | - SDS-M0460: IP55

Product Standards
Applicable Standards

IEC 60092-504: 2016
EN 54-2:1997+A1:2006
BS EN 54-4:1998
FSS Code 2015: Chapter 10

Similar Products