9907-997, Valve, Liquid Fuel Shutoff Valve
Piping System Components
Valve, Liquid Fuel Shutoff Valve
9907-997
Product Description
The Woodward High Speed Liquid Fuel Shutoff Valve is a Three-Way, Two-Stage Valve, designed to provide fuel bypass in 0.100 seconds or less after termination of the solenoid current. The valve has been designed for Fail-Safe Operation. Loss or Termination of the Electrical Signal will result in all fuel delivery to the valve being bypassed to the return system. The Valve is compatible with most Liquid Fuels, including Diesel Fuel, Methanol, Ethanol, Jet "A", Kerosene, #2 Home Heating Oil, Heated Light Crudes, and Residuals. The Valve will accommodate contaminated fuels within prescribed limits. For General Operation Notes and Warnings, General Information, Installation, Principles of Operation, Service Options, Ilustrations and Tables see Manual 40148C.
Product Ratings
Maximum Allowed Design Fuel Pressure: 1233 psig (8501 kPa); Maximum Fuel Inlet Operating Pressure: 1233 psig (8501 kPa); | Proof Pressure: 1800 psig (12411 kPa); | Burst Pressure: 6000 psig (41369 kPa); | Fuel Temperature Range: 0 F to 250F (-18C to 120C);
Applicable Standards
Manufacturer's Standard, US Mil-Std-167-1A, Type 1 Vibration, 2005.